Hood and Duct System Requirements

  • A UL 300 compliant system shall be installed.
  • Plans with cut sheets shall be presented for review. Contact the Fire Prevention Bureau to check the plans.
  • The test system shall be connected to the fire alarm system if the occupancy is equipped with one.
  • Pull station shall be 10’ away and in the direction of egress.
  • Gas shall turn off when activated.
  • Any electrical outlets under the hoods shall turn off if the system is activated.
  • A Class “K” fire extinguisher is required.
  • A plan review fee of $75 per hood applies.